1.7 Ventilation Requirements
Nor-Ray-Vac heaters are installed as flued
appliances in accordance with the relevant
national requirements in the country of
installation.
In buildings having an air change rate of less
than 0.5 per hour, additional ventilation is
required. For detailed information, please see
BS6896 section 5.2.2.2.1
Natural Ventilation
Low level ventilation openings with a free area
of at least 2cm²/kW shall be provided. See
BS6896 section 5.2.2.2.2.1.
1.8 Exhaust and Air Inlet - Options
1.8.1 Horizontal discharge
Considerations.
The vacuum fan must be located as
shown in the layout drawing.
The vacuum fan must have a bottom hor-
izontal discharge.
The fan should be fitted to the mounting
platform which is fixed to the wall or
building structure. Alternatively, the fan
can be suspended from the roof
structure, via drop rods (not supplied) and
mounted on base frame. (Anti-vibration
mountings are fitted between the fan and
the mounting platform/base frame.
For full details of parts and installation,
please refer to section 2.9.3
1.8.2 Vertical discharge