THE LOCAL RELAY UNIT houses an inverter. This
converts the 230V single-phase input into a
three-phase 230V output. The inverter provides a
soft start to the motor, which extends the motor life
by minimising the start current.
Inverter
Local Relay
Unit
Supply via Isolator
230V 50Hz 1 Pha
SUPPLY VIA ISOLATOR
ELECTRICAL INPUT
230V 1P 22A
230V 1P 22A
230V 1P 30A
FAN TYPE
B80
B160
B300
Burners
Zone A
LL NN
U V W1 342
Drawing No. : 900287 R6
Supply to inline
burners
Exhaust
Fan
4-Core Armoured or
Screened Cable 1.5mm²
FAN MOTOR
230V 3-Phase Supply.
Motor must be wired DELTA
3 Phase
Isolator
MPORTANT
For Inverter panels only
(fan types B80 / B160 & B300):
MAXIMUM length of cable between inverter
and fan is 5m (EMC class A building) or
10m (EMC class B building).
N.B. if in doubt, do not exceed 5m.
(HEAT 1 OUTPUT)
(LIVE)
(NEUTRAL)
NOTES:
REMOTE SWITCH INPUTS
should be connected by 6A mains
Max length is 100m.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
Connect to B0 & B2 for remote
OFF (ie door interlock. remote
frost etc).
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
REMOTE SENSOR(s) may be
placed at a max distance of 100m
from the control unit, using
screened 6A mains* cable.
Wiring should be kept separate
from mains wiring to minimise
noise pick up. Set within Engineers
functions for remote sensor.
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
Low Voltage
+15V DC
Black Bulb
Sensor
(FAN CIRCUIT)
(FAN CIRCUIT)
Volt free
Fan Trip
Indication
by others
Note: Connection to the
burners MUST be made
via a 3A fused spur.
!
!
FUSE RATING
!
41 40 95 1/L 2/N 106
B1 B0 B2 S/R0S/R1
C
SmartCom
Singlezone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
eg Door
Remote OFF
(where applicable)
Remote ON
(where applicable)
eg B.M.S.
Figure 4.l. NRV Schematic interconnecting wiring. B80, B160 and B300 three phase fans
controlled by SmartCom3 via single phase Inverter panel. (single zone shown)